| Normal Opeation Conditions
1. Ambient Air temperature: Ambient air temperature
ranges from-5°C~+40°C,not exceeding 35°C averagely
in 24 hours.
2. Location: Installation location can not exceed 2000 meters
above sea level.
3. Air conditions: Relative humidity in the installation place
can not exceed 50%when the air reaches the highest temperature
+40°C, the average minmum temperature when it is the wettest
can not exceed 25°C, Relative humidity not exceeding 90%.
4. Installation Conditions: Installation is divided into grade
II,grade III
5. Installation Pollution Grade: Installation pollution grade
is grade II.
6. Installation Conditions: Magnetic field outside the installation
place can not exceed 5times of the site of terrestrial magnetism
in all direction. Normally speaking, RCBO should be mounted
vertically. If the operation handle puts through power source
upward, there should be no notable impact and vibration in
the installation place.
Notice
1. Leakage Protection function of RCBO is tested and adjusted
by the manufacture, users can not open the products at random
during usage.
2. After using RCBO for a certain time (normally one month),
test button should be pressed once in a state of making the
circuit to check whether the function of RCBO is normal and
reliable (press test button once, the RCBO can break off once
). If abnormal, it should be unloaded and sent to the manufacturer
for repair.
3. RCBO must not be wetted or soaked by rain, snow or water
during the course of transportation, storage and usage.
Dimension And Mounting
|